 Phase Failure Relays
WILMARTM Protective Relays - 1000 Series
Function: 47
* ANSI/IEEE C37.90-1978
TERMINAL STRIPS #6 - 32 SCREWS
* UL file No. E58048 * CSA file No. LR61158 Phase failure relays protect motors, equipment and personnel from damage or injury caused by open phase, reversed phase sequence, or low voltage in a three phase system. Models are available for 50 and 60 Hz with voltages up to 575 volts. Motor control switchboards are a common application. Operation: The contacts of the relay will close only when it senses normal conditions of three phase power at the proper phase sequence. The relay contacts will remain in their normally open position (de-energized) when voltage with incorrect phase sequence is applied, one or more phases are open, or at undervoltage condition.
3 13/16
Note: Dimensions in inches. Multiply values by 25.4 for dimensions in mm.
Part Number
Nominal Voltage ............................. Voltage Drop-Out ........................... Pick-Up to Drop-Out Differential .... Ambient Operating Temperature .... Temperature Drift ........................... Time Delay ..................................... Output Contacts ............................. Contact Ratings ..............................
3.0 1 /2 3 /8 7 3
2 3/4 1/2 3
11/64" DIA. 4 MTG. HOLES
PART NUMBER SELECTION
PART NUMBER SELECTION
Sample Part No. 1004X Type: 1001 = 120 V, 60 Hz, 3 phase,L-L 1007 = 208 V, 60 Hz, 3 phase, L-L 1002 = 230 V, 60 Hz, 3 phase,L-L 1012 = 300 V, 60 Hz, 3 phase, L-L 1013 = 350 V, 60 Hz, 3 phase, L-L 1003 = 380 V, 50 Hz, 3 phase, L-L 1004 = 460 V, 60 Hz, 3 phase,L-L 1005 = 525 V, 60 Hz, 3 phase,L-L 1006 = 575 V, 60 Hz, 3 Phase, L-L Mounting: X = Flange Blank - Stud Consult factory for additional models and options Notes: 1. Remove screw for access to the undervoltage adjustment. 2. Clockwise rotation of the adjustment potentiometer will raise the drop-out voltage.
PRODUCT SPECIFICATIONS
1000 Series
See Table 75% to 100% of nominal, screwdriver adjustable 3% approx. -40oC to +70oC
1%
See Curve One set, normally open 10 amp at 28 VDC resistive 10 amp at 230 VAC resistive
30
Tyco Electronics / www.tycoelectronics.com / Factory Direct Technical Support: 800-253-4560, ext. 2023 (U.S., Canada, Mexico) or 805-220-2020, ext. 2023 (International)


▲Up To Search▲   

 
Price & Availability of 1006

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X